Inspection
Inspection Details
Equipment ID
17310
17310
Inspection Date
8/17/2017
8/17/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
Location
Harrahs Casino
784 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
784 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
Owner
Hollywood Casino St. Louis
777 Casino Dr, Maryland Heights, MO 63043
777 Casino Dr, Maryland Heights, MO 63043
Billing
Attn: Hollywood Casino St. Louis
777 Casino Center Dr, , MO 63043
777 Casino Center Dr, , MO 63043
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Weight rods loose on counter weights | 7/30/2019 |
| conversion | conversion | n/a | No | No | Replace missing counterweight roller | 7/30/2019 |
| conversion | conversion | n/a | No | No | Alarm bell does not work | 7/30/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car runs with car door open 4" maximum is 2" | 8/6/2018 |
| conversion | conversion | n/a | No | No | Car door restrictor does not work. | 7/30/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab emergency lights do not work | 8/6/2018 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Weight rods on counterweight are loose. | 7/30/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 10/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Outer insulating jacket is coming off of traveling cable under car, no conductors exposed. Repair or replace | 7/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Traveling cable is damaged in several spots and needs to be replaced. Re-inspection required | 7/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/20/2026 |