Inspection
Inspection Details
Equipment ID
2687
2687
Inspection Date
8/16/2021
8/16/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
54a0ae25-c361-42d6-9ce6-78218a09f59b
54a0ae25-c361-42d6-9ce6-78218a09f59b
Location
Fine Arts Bldg
5015 HOLMES ST, KANSAS CITY, MO
Phone: (816) 235-1363
5015 HOLMES ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: Chauncy Kuhl
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | replace the emergency light battery, it is dead | 5/29/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide access to the complete MCP in the machine room according to 8.6 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag expired | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | the alarm bell did not work with the 110 volt power off | 5/21/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag is from 2015, it is to be inspected and tagged annually. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | The alarm bell did not work when the 110 volt power was turned off, elevator is not equipped with an alarm bell that works on battery voltage | 5/18/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean the pit, there is oil on the floor | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019 |