Inspection
Inspection Details
Equipment ID
2703
2703
Inspection Date
8/16/2021
8/16/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
fd313f4d-7afb-47b6-b885-a9f26ae58ac5
fd313f4d-7afb-47b6-b885-a9f26ae58ac5
Location
School of Dentistry
650 E 25TH ST, KANSAS CITY, MO
Phone: (816) 235-1363
650 E 25TH ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: Chauncy Kuhl
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | need to have two working ligh fixtures in the car | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Repair pit light, it did not work. possible burnt out bulb | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Replace the emergency light battery, it is dead | 6/4/2020 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current copy of the state operating certificate in the machine room | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide access to the complete MCP in the machine room according to 8.6 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | bottom landing freight door hoistway access pull chain cover lock is broken and needs to be repaired | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | replace the emergency light battery, it is almost dead | 8/16/2021 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. the one in the room is from 2016 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | could not find the any of the oil record logs, logs are to be kept in the machine room for 5 years. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2017 | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | Replace missing pull strap on level B hoistway door | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Water in the pit, unclogged floor drain in the pit | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light does not work no lightbulb in fixture, replace lightbulb | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Recovery pump in the pit needs to be replaced with a 5 gallon bucket per state memo 6 (8.6.5.5.2) |