Inspection
Inspection Details
Equipment ID
15161
15161
Inspection Date
11/5/2021
11/5/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
3b8e0af0-dca4-4224-ba53-2abf42e01dd1
3b8e0af0-dca4-4224-ba53-2abf42e01dd1
Location
The Saum & Hutcheson Arms Apartments
1919 S Grand Blvd, St. Louis, MO
Phone: (314) 685-1130
1919 S Grand Blvd, St. Louis, MO
Phone: (314) 685-1130
Owner
Attn: The Saum & Hutcheson Arms Apartments
The Saum & Hutcheson Arms Apartments
1919 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 685-1130
The Saum & Hutcheson Arms Apartments
1919 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 685-1130
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | x | No emergency alarm bell. Red tag unit until all violations are repaired | 11/5/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Install escape hatch cover lid. To be bolted shut to open from cartop without special tools | 12/29/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean debris out of pit, pit shall remain clean & dry | 12/29/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Pit deeper than 4 ft, install pit ladder. Extend 4 ft above basement landing | 12/29/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light of at least 5 FC shall be installed in pit, with switch accessible from basement door | 12/29/2021 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | Basement hoistway door is plexiglass and its broken, replace with laminate glass | 12/29/2021 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Annunciator needs cover | 12/29/2021 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Close lattice at top of cab with solid non combustible material | 12/29/2021 | ||
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | x | x | Final limit does not function, Red tagged, Re-inspection required | 1/30/2023 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | x | x | Gate switch does not function. Red tagged, Re-inspection required | 1/30/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete, need to do a safety soft set. Re-inspection required | 1/30/2023 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean debris out of pit | |||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Need to install pit ladder. Pit deeper than 4 ft, extend ladder 4 ft above basement landing | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Annunciator needs a cover | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | Close lattice at top of cab with solid, non-combustible material |