Inspection
Inspection Details
Equipment ID
9708
9708
Inspection Date
11/5/2021
11/5/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
82fb0cc4-26ba-4a95-811c-91e2c395815f
82fb0cc4-26ba-4a95-811c-91e2c395815f
Location
Mosaic Life Care of St Joseph
528 N 8TH ST, SAINT JOSEPH, MO
Phone: (816) 271-7791
528 N 8TH ST, SAINT JOSEPH, MO
Phone: (816) 271-7791
Owner
Attn: St. Joseph Downtown Development LLC
St. Joseph Downtown Development LLC
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
St. Joseph Downtown Development LLC
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | emergency light and bell do not work | 10/29/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Post emergency evacuation of passengers procedure inside machine | 11/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines need to drain into pit collection containers of no more than 5 gallons | 11/17/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 12/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines need to drain into pit collection containers | 12/18/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 12/18/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking and non-defeatable | 12/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance record log not up to date | 12/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines shall be ran to pit collection container, not back to hydraulic tank. | 12/18/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/18/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-closing and self-locking. (third notice) | 12/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines need to be ran to pit collection containers. (third notice) | 12/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not operate | 2/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/14/2023 |