Inspection
Inspection Details
Equipment ID
22155
22155
Inspection Date
11/8/2021
11/8/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Brian Heine
Brian Heine
Relief Valve Pressure
Slide
SOFT SET
SOFT SET
Governor Rope Pull
SOFT SET
SOFT SET
Door Closing Force
19
19
External ID
7b07c12b-e750-4b07-8ed6-9b7265b3569e
7b07c12b-e750-4b07-8ed6-9b7265b3569e
Location
The Broadway Federal
339 Broadway St, Cape Girardeau, MO
Phone: (573) 576-1306
339 Broadway St, Cape Girardeau, MO
Phone: (573) 576-1306
Owner
Attn: APG Limited, LLC
APG Limited, LLC
PO Box 2132, Cape Girardeau, MO 63702
Phone: (573) 207-4288
Email: lindsey@rentathena.com
APG Limited, LLC
PO Box 2132, Cape Girardeau, MO 63702
Phone: (573) 207-4288
Email: lindsey@rentathena.com
Billing
Attn: Janus Development Group LLC
Janus Development Group LLC
PO Box 2132, Cape Girardeau, MO 63702
Phone: (000) 000-0000
Email: christy@zrgmail.com
Janus Development Group LLC
PO Box 2132, Cape Girardeau, MO 63702
Phone: (000) 000-0000
Email: christy@zrgmail.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 8.11.2.1.1(n) | Yes | No | Replace the missing low cab ventilation trim on (2) walls. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Remove all foreign wires and cables passing through the elevator machine room. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Seal all machine room penetrations. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Remove wire mesh window and enclose hole. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Steam heater in machine room, if working repair to prevent leaking. If not in use, remove. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Confirm climate control in elevator machine room. Heat & A/C. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | Provide code compliant machine room lighting of 19fc. Currently measured at 3.7fc. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car car emergency telephone shall work with 24/7 support. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | Yes | No | 2.10.2 Provide toe board on car top. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Provide a sump pump in the pit. Test the sump pump once installed. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Seal all penetrations in the hoistway. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide a counterweight runby sign in the pit. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | 2.19 - Provide unintended movement test. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.10.2.2.2(cc)(1) | Yes | No | Provide ascending car overspeed test. | 11/8/2019 |