Inspection
Inspection Details
Equipment ID
8182
8182
Inspection Date
10/4/2021
10/4/2021
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
na
na
Slide
Governor Rope Pull
Door Closing Force
External ID
acaa5370-772d-49de-bf30-f2180b9f7ac6
acaa5370-772d-49de-bf30-f2180b9f7ac6
Location
Autumn View Gardens
11210 SCHUETZ RD, SAINT LOUIS, MO
Phone: (314) 993-9888
11210 SCHUETZ RD, SAINT LOUIS, MO
Phone: (314) 993-9888
Owner
Attn: Autumn View Gardens at Schuetz Rd
Autumn View Gardens at Schuetz Rd
11210 Schuetz Rd, St. Louis, MO 63146
Phone: (314) 993-9888
Email: SCHbilling@ba.org
Autumn View Gardens at Schuetz Rd
11210 Schuetz Rd, St. Louis, MO 63146
Phone: (314) 993-9888
Email: SCHbilling@ba.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Hold position phase 2 fire service | 12/4/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Disabled car door restrictor. | 1/14/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV not sealed. Perform OSV test on or before next annual inspection. | 10/25/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)9 | No | No | Reverse phase relay needs to be installed to prevent reverse operation of the motor or loss of phase. | 10/25/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire Use Stairs” is missing. Install signage that conforms to the building code this elevator was installed to meet. | 10/25/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/25/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 10/25/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 9/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 11/25/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Testing of OSV needs to be performed to complete this inspection. Re-inspection required | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency battery lowering device did not work, needs repaired. Re-inspection required |