Inspection
Inspection Details
Equipment ID
23376
23376
Inspection Date
7/23/2018
7/23/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
a3bb3e58-98a1-443a-91a5-a0e5355ee31b
a3bb3e58-98a1-443a-91a5-a0e5355ee31b
Location
University of St Louis Grand Hall
3605 LACLEDE AVE, SAINT LOUIS, MO
3605 LACLEDE AVE, SAINT LOUIS, MO
Owner
St. Louis University
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
Billing
Attn: St. Louis University
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Test cab two way communitcation | 7/16/2020 |
| conversion | conversion | n/a | No | No | Test recall from fire command center switch | 7/16/2020 |
| conversion | conversion | n/a | No | No | Relocate all elevator lobby smoke detectors further that 2 ft from car door | 7/16/2020 |
| conversion | conversion | n/a | No | No | Extend pit ladder to the required 48 inch height above access sill | 7/16/2020 |
| conversion | conversion | n/a | No | No | Reduce counterweight runby to the pit posted demension | 7/16/2020 |
| conversion | conversion | n/a | No | No | Plug all hoistway to machine room penetrations | 7/16/2020 |
| conversion | conversion | n/a | No | No | Hoistway access switches inoperative | 7/16/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Install all corridor call station pictographs. | 7/23/2018 |
| conversion | conversion | n/a | No | No | Mark floor numbers on corresponding hoistway doors, car side | 7/16/2020 |
| conversion | conversion | n/a | No | No | Install all hoistway duct covers including any for car top | 7/16/2020 |
| conversion | conversion | n/a | No | No | Install 2nd pit stop switch 47 in from pit floor | 7/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.2 - Stop switches | 8.11.2.1.1(b) (Re-Inspection) | No | No | In car stop switch shall be overridden when car is in flight on Phase 1 Fire Service. Reinspection Required. | 7/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | mergency power must be tested. Re-inspection required | 12/17/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.27 | Yes | No | Need to perform the required Cat 1 emergency generator testing to complete the annual testing. Re-inspection required | 7/30/2025 |