Inspection
Inspection Details
Equipment ID
23272
23272
Inspection Date
10/19/2021
10/19/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
Slide
1.5" @ 150 fpm
1.5" @ 150 fpm
Governor Rope Pull
40/180
40/180
Door Closing Force
21F/17R
21F/17R
External ID
81ca7747-9d48-4a02-ad4c-d1399baff28e
81ca7747-9d48-4a02-ad4c-d1399baff28e
Location
Anthology of Clayton
8825 EAGER RD, SAINT LOUIS, MO
Phone: (314) 961-1700
8825 EAGER RD, SAINT LOUIS, MO
Phone: (314) 961-1700
Owner
Attn: Tony Cwiklowski
Anthology of Clayton
8825 Eager Rd, St. Louis, MO 63144
Phone: (314) 961-1700
Email: tcwiklowksi@anthologyseniorliving.com
Anthology of Clayton
8825 Eager Rd, St. Louis, MO 63144
Phone: (314) 961-1700
Email: tcwiklowksi@anthologyseniorliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 10/26/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Weights shall not be stored on the car top. | 2/18/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | The tail sheave switch shall be wired per the manufactures’ specifications. | 1/1/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/1/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | An ABC fire extinguisher with a current test tag shall be mounted convenient to the top landing door. | 1/1/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.27 - Rope fastenings | 2.20 | Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 8/14/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Clean the pit of oil, dirt, and debris. | 8/14/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/13/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/14/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. Note: The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. | 1/30/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | x | Phase two fire service operation shall operate as required. The doors are not closing some times on phase two and other times, the car reverts to phase one when it should not. | 1/30/2025 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Button covers inside car are missing. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept clean. | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | x | Siprator cable at 1R landing is broken and needs to be replaced. |