Inspection
Inspection Details
Equipment ID
5793
5793
Inspection Date
10/21/2021
10/21/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
d4478cc2-a272-4ec6-a271-1c89ec57f9c7
d4478cc2-a272-4ec6-a271-1c89ec57f9c7
Location
Boder Building
105 S 4TH ST, SAINT JOSEPH, MO
Phone: (816) 233-7003
105 S 4TH ST, SAINT JOSEPH, MO
Phone: (816) 233-7003
Owner
JaJo Investment LLC
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
Billing
Attn: JaJo Investment LLC
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Pit can is overflowing. Pit can shall not be permitted to overflow. | 6/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove hydraulic oil from pit floor. Pit floors shall be kept clean and dry. | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide written documentation inside machine room of quantity of hydraulic fluid added to system and emptied from pit can. | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance Control Plan records for the elevator need to be viewable on site. | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records on site | 10/28/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 10/28/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking and non-defeatable | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide certified type ABC fire extinguisher inside the machine room | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace plunger seals. Plunger seals leak excessively and pit collection container has overflowed. | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell do not operate | 10/21/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell do not operate. |