Inspection
Inspection Details
Equipment ID
2212
2212
Inspection Date
11/10/2021
11/10/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
85f9702c-e143-4f70-92a6-4669da99d285
85f9702c-e143-4f70-92a6-4669da99d285
Location
Mosaic Life Care
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
Owner
Attn: St. Joseph Downtown Development LLC
St. Joseph Downtown Development LLC
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
St. Joseph Downtown Development LLC
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter instructions next to hall fire keyswitch | 11/17/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post correct firefighter instructions inside elevator | 11/17/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine | 11/17/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace incorrect firefighter instructions on car operating panel | 11/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Install FEO-K1 keyswitches. All elevators in the same building shall be operable by the key | 11/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Momentary operation of door open button allows doors to fully open. 14 days to fix or red tagged | 11/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace leaking plunger seal. | 11/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove hydraulic oil from pit floor | 11/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Smoke sensitive door reopening device does not disable on phase 1 operation. 14 days to fix or red tagged. | 11/8/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 11/11/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test operation of elevator on emergency power with an inspector present | 11/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Door reopening device does not disable on phase 1 recall. | 11/10/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Momentary operation of door open button allows doors to fully open | 11/10/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test operation of elevator on emergency power with inspector present | 12/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace incorrect firefighter operating instructions on car operating panel | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post firefighter instructions next to hall fire keyswitch | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove rags from machine room floor | 12/7/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test operation of elevator on emergency power | 11/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | MRL not up to date | 12/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace plunge seal. Seal leaks excessively | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove oil from pit floor. | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Standby power selection keyswitch on lobby panel not identified. Replace identification keyswitch bezel. | 1/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test emergency power operation | 12/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/5/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The emergency power was not tested. | 11/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Keyswitch bezels are illegible. | 11/13/2025 |