Inspection
Inspection Details
Equipment ID
7663
7663
Inspection Date
11/23/2021
11/23/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
Slide
Incomplete
Incomplete
Governor Rope Pull
160/650
160/650
Door Closing Force
22
22
External ID
95bd2009-f5e7-4105-9554-de2862dac416
95bd2009-f5e7-4105-9554-de2862dac416
Location
Humboldt Bldg
539 N Grand Blvd, St. Louis, MO
Phone: (314) 239-3217
539 N Grand Blvd, St. Louis, MO
Phone: (314) 239-3217
Owner
Attn: Fox Associates
Fox Associates
527 N Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Fox Associates
527 N Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | Repair machine room lights. | 5/12/2020 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm bell does not work on emergency 110v power or normal power | 12/30/2021 | |
A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | x | x | Safety Operated Switch attached to governor rope is broken and not operable. RED TAG | 12/30/2021 |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Inspection is incomplete, must complete all weight testing and spinning the governor. Spring buffers do not need compressed. | 12/30/2021 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Brake failed to hold capacity load. Car removed from service. | 2/11/2022 | |
A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 205.11 | x | x | Car safety wind up drum cable had 2 wraps left on the drum after setting the safeties. Repair or replace cable or safeties | 3/24/2022 |
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Fire extinguisher in machine room is expired, needs serviced or replaced | 12/7/2022 | ||
A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | Machine room 110 supply shall be installed to the NFPA 70 with receptacle box mounted securely to the wall | 12/7/2022 | ||
A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | Patch/repair all holes in the hoistway walls. Hole in hoistway wall about 8' to 10' looking through to the back of interior sheet rock office wall. Also, other smaller holes. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency alarm bell shall be operational. | 2/21/2024 | |
A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | x | Holes need to be patched in hoistway. (Repeat Violation) Re-Inspection required. | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency alarm bell shall be operational. (Repeat Violation) Re-Inspection required. |