Inspection
Inspection Details
Equipment ID
6250
6250
Inspection Date
11/24/2021
11/24/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
4d01e6ed-3601-4bf1-a0b0-e8234930e744
4d01e6ed-3601-4bf1-a0b0-e8234930e744
Location
Leaverton Hall
4525 DOWNS DR, SAINT JOSEPH, MO
Phone: (816) 271-4417
4525 DOWNS DR, SAINT JOSEPH, MO
Phone: (816) 271-4417
Owner
Attn: MO Western State University
MO Western State University
4525 DOWNS DR, SAINT JOSEPH, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
MO Western State University
4525 DOWNS DR, SAINT JOSEPH, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door reopening device is connected to the car lighting circuit | 11/24/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to corridor call station at each landing | 4/7/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter instructions on car operating panel | 4/7/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace illegible firefighter instructions next to hall fire keyswitch | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing lamps and lens for car direction lantern. | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 4/7/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate inside the machine room | 4/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing lamps and lens on car direction lantern. | 11/26/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | No pit lighting. Repair or replace pit light fixture and/or associated wiring. | 11/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No 2022 maintenance record log | 11/26/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.14.2 | Yes | Yes | Elevator failed set test after annual pressure testing of the hydraulic system. Replace hydraulic cylinder | 11/27/2024 |