Inspection
Inspection Details
Equipment ID
14756
14756
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Douglas Dalton
Douglas Dalton
Relief Valve Pressure
345
345
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
a58c96ba-e577-4ca9-a192-fb9276c1bc0c
a58c96ba-e577-4ca9-a192-fb9276c1bc0c
Location
Arcaidia Valley Medical
200 ST. MARY ST, PILOT KNOB, MO
200 ST. MARY ST, PILOT KNOB, MO
Owner
Cimms Board
200 ST. MARY ST, PILOT KNOB, MO 00000
200 ST. MARY ST, PILOT KNOB, MO 00000
Billing
Attn: Cimms Board
PO BOX 339, PILOT KNOB, MO 63663-0339
PO BOX 339, PILOT KNOB, MO 63663-0339
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | Need maintenance control program. A17.2.2.41 | 6/16/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. | 6/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records in machine room. | 6/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current tested fire extinguisher in the elevator machine room. | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Cylinder packing is worn and leaking, repair as needed. | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit.(water/oil) | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Provide means to prevent the accumulation of groundwater in the pit. Rust prevention of pit equipment needed. | 3/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone is not working. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The is no fire extinguisher in the machine room | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from the pit | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Smoke detector is hanging down from machine room ceiling. | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone is not working in the elevator. Re-inspection required | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The is no fire extinguisher in the machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from the pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Smoke detector is hanging down from machine room ceiling. |