Inspection
Inspection Details
Equipment ID
17347
17347
Inspection Date
11/2/2021
11/2/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
286c7b1e-ebcd-4305-9aee-5b4200d0e5a9
286c7b1e-ebcd-4305-9aee-5b4200d0e5a9
Location
Sullivan Place Apartments West
3014 N 25th St, St. Louis, MO
Phone: (314) 269-8000
3014 N 25th St, St. Louis, MO
Phone: (314) 269-8000
Owner
Attn: Sullivan Place Apartments
Cohen Esrey
6800 W 64th St, Ste 101, Overland Park, KS 66202
Phone: (000) 000-0000
Cohen Esrey
6800 W 64th St, Ste 101, Overland Park, KS 66202
Phone: (000) 000-0000
Billing
Attn: Ashley Gould
Sullivan Place Apartments
3015 N 23rd St, St. Louis, MO 63107
Phone: (314) 932-5006
Email: Ashley.Gould@LiveWellCE.com
Sullivan Place Apartments
3015 N 23rd St, St. Louis, MO 63107
Phone: (314) 932-5006
Email: Ashley.Gould@LiveWellCE.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Existing cab emergency telephone does not work, and shall be repaired and tested. | 2/14/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 7/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/2/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 5/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/27/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve within 90 days. | 5/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 7/27/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Elevators that are equipped to operate on emergency power (noted on unit as having EP) shall be tested with no load in the car, operating on emergency power, annually. | 2/7/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 2/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/16/2026 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall be not be stored in the machine room (fan, water hose, paint, etc). | 2/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/16/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency power operation shall be tested. | 2/16/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two way communication device is not functioning properly and needs repair. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating certificate shall be displayed in the machine room in a non-combustible frame. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current ABC fire extinguisher shall be provided in machine room. | |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 204.2(a) Material for Car Enclosure Linings, and floor Coverings. | Yes | No | Replace missing and broken up floor tiles in the car as they present a trip hazard. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 207.8 | Yes | No | Emergency power operation could not be tested. |