Inspection
Inspection Details
Equipment ID
7903
7903
Inspection Date
11/18/2021
11/18/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
c69162af-dd73-466d-a257-b31bf3e0e3e2
c69162af-dd73-466d-a257-b31bf3e0e3e2
Location
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO
Phone: (000) 000-0000
4960 Laclede Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Royals Oak
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Richard.Woolard@reachltc.com
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Richard.Woolard@reachltc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Fire caulk hole in the machine room wall. | 5/12/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Fire caulk hole in the pit wall. | 5/13/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Provide an emergency phone in the cab. | 7/3/2019 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Properly secure the car top exit. | 5/12/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Make the car top run button operational. | 5/12/2023 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Secure the smoke detector at top of hoistway. | 7/3/2019 | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Properly guard the pit light. | 5/12/2023 | ||
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | Fire caulk hole in machine room wall. (Repeat violation) | 5/12/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Fire caulk hole in pit wall. (Repeat Violation) | 5/12/2023 | ||
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 1001.2(c)(12) | Properly secure car top exit. (Repeat Violation) | 5/12/2023 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | An in car emergency phone shall be provided. (Repeat Violation) | 10/13/2020 | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Properly guard the pit light. (Repeat Violation) | 5/12/2023 | ||
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | Replace missing hoistway door sight guard at 4th floor. | 5/12/2023 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The machine room shall be kept clean and all non-elevator related materials shall be removed from the machine room. | 5/12/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean. Clean the pit. | 5/12/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The emergency lighting shall be operational. | 11/18/2021 | |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | Fire caulk hole in machine room wall. | 5/12/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Fire caulk hole in pit wall. | 5/12/2023 | ||
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 1001.2(c)(12) | Properly secure car top exit. | 5/12/2023 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | An in car emergency phone shall be provided. | 11/18/2021 | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Properly guard the pit light. | 5/12/2023 | ||
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | Replace missing hoistway door sight guard at 4th floor. | 5/12/2023 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 5/12/2023 | ||
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 5/12/2023 |