Inspection
Inspection Details
Equipment ID
15700
15700
Inspection Date
7/20/2018
7/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
0ee0b463-db08-4777-9bef-333073a2d45b
0ee0b463-db08-4777-9bef-333073a2d45b
Location
Harris Stowe Early Childhood Development
10 N COMPTON AVE, SAINT LOUIS, MO
10 N COMPTON AVE, SAINT LOUIS, MO
Owner
Harris Stowe State College
3026 LACLEDE AVE, SAINT LOUIS, MO 63103-2136
3026 LACLEDE AVE, SAINT LOUIS, MO 63103-2136
Billing
Attn: Harris Stowe State College
3026 LACLEDE AVE, SAINT LOUIS, MO 63103-2136
3026 LACLEDE AVE, SAINT LOUIS, MO 63103-2136
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Existing cab emergency telephone doe not work and shall be repaired and tested. | 7/20/2018 |
| conversion | conversion | n/a | No | No | Phase 1 key station has a broken jewel bezel on the fireman's hat indicator, said jewel shall be replaced. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Firemans Phase 1 bezel is missing and shall be replaced. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation date of 2008, the overspeed valve is due for a category 5 test on or before the next annual inspection. | 9/11/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed within 90 days. | 9/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Mo State operating certificate is expired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | No | No | Second floor button is broken and shall be repaired or replaced. |