Inspection
Inspection Details
Equipment ID
13809
13809
Inspection Date
12/9/2021
12/9/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
18833eb4-8fa1-4ef2-82f1-d922be571a6b
18833eb4-8fa1-4ef2-82f1-d922be571a6b
Location
The Learning Center
900 Hornet Dr, Hazelwood, MO
Phone: (314) 285-1239
Email: gqclodfelter@ssdmo.org
900 Hornet Dr, Hazelwood, MO
Phone: (314) 285-1239
Email: gqclodfelter@ssdmo.org
Owner
Attn: Toby Clodfelter
Special School District of Saint Louis County
12110 Clayton Road, Saint Louis, MO 63131
Phone: (314) 989-8100
Alt Phone: (314) 285-1239
Special School District of Saint Louis County
12110 Clayton Road, Saint Louis, MO 63131
Phone: (314) 989-8100
Alt Phone: (314) 285-1239
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | No | Yes | Fire sprinklers and heat detectors have been added to the elevator hoistway and machine room. Shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required. | 5/20/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 4/6/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:Phase I did not initiate when the fireman's emergency service key was turned to the “ON” position. The elevator was placed out of service. No further testing was performed, a full reinspection will be required. | 5/20/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 4/6/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 4/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. | 11/6/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car “door open” button would not open the elevator car door. Repair or replace car door open button. | 12/17/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The car doors will not open on phase II operation. Elevator was red tagged and placed out of service. Reinspection is required. | 12/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Repair inoperative door restrictor. | 2/10/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety code concern. Without motion the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch | 4/6/2023 |