Inspection
Inspection Details
Equipment ID
11244
11244
Inspection Date
8/15/2018
8/15/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Jeremiah Dugger
Jeremiah Dugger
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
14aece0c-4bb8-46e0-91a0-bbd19ddbe557
14aece0c-4bb8-46e0-91a0-bbd19ddbe557
Location
Monarch Cove Condos
100 MONARCH CV, LAKE OZARK, MO
100 MONARCH CV, LAKE OZARK, MO
Owner
Monarch Cove Condo Owners Association
PO BOX 189, OSAGE BEACH, MO 65065-0189
PO BOX 189, OSAGE BEACH, MO 65065-0189
Billing
Attn: PMP
PO BOX 189, OSAGE BEACH, MO 65065-0189
PO BOX 189, OSAGE BEACH, MO 65065-0189
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Phase I operating instructions and key switch bezel need to be replaced, they are illegible | 9/17/2021 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Door to equipment room needs to be self closing and locking | 9/17/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit light is out | 9/17/2021 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Access to machine space is dangerous. Need steps from gate to the ground outside. | 9/17/2021 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | Extension cord run from somewhere else thru machine room needs to be removed and hole patched in wall | 9/17/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All required maintenance records need to be supplied by Otis | 5/7/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door not self locking or closing | 5/7/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | very steep slop to climb to get to machine room. Install different access | 5/7/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | maintenance records | 5/7/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | machine room door not self closing or locking | 5/7/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Very steep grass slope, dangers to travel, change access. Gate in handrail ? | 5/7/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | MACHINE ROOM DOOR IS REQUIRED TO BE SELF LOCKING | 5/7/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | NEEDS STAIRS OFF OF LANDING TO ACCESS MECHINE ROOM. CURRENTLY A 5' JUMP DOWN | 5/7/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | BAD KEY SWITCH IN HALLWAY | 5/7/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | PHASE 1 FIRE SERVICE INSTRUCTIONS NOT LEGIBLE | 5/7/2026 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | NEEDS IN CASE OF FIRE USE STAIRS SIGNS | 5/7/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE IS NOT WORKING | 5/7/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | MUST HAVE A CURRENT TEST TAG | 5/7/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE MUST BE MADE OPERABLE NO DIAL TONE |