Inspection
Inspection Details
Equipment ID
15025
15025
Inspection Date
12/8/2021
12/8/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
243b7e8a-896f-4e97-83be-cb814388b202
243b7e8a-896f-4e97-83be-cb814388b202
Location
Mosaic Life Care
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
Owner
Attn: St. Joseph Downtown Development LLC
St. Joseph Downtown Development LLC
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
St. Joseph Downtown Development LLC
5325 Faraon St, St. Joseph, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | Door pressure exceeds 30# | 12/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Install FEO-K1 keyswitch. All elevators in the same building shall have firefighter keyswitches operable by the same key | 10/24/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power with an inspector present | 12/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | No audible signal during phase 1 recall | 10/24/2023 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door force exceeds 30# | 10/24/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | MRL not up to date | 2/1/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power | 10/24/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | No audible signal during fire recall | 12/13/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test emergency power operation | 12/13/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace cylinder on fire recall keyswitch. The cylinder turns past the on position. | 1/5/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | no audible signal on fire recall | 1/4/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The emergency power was not tested. | 11/13/2024 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1002.3d | Yes | No | Machine brake not holding 125%, repair. | 11/13/2025 |