Inspection
Inspection Details
Equipment ID
9349
9349
Inspection Date
6/11/2018
6/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
a90156c1-40ad-42b7-a6b8-258b210a0838
a90156c1-40ad-42b7-a6b8-258b210a0838
Location
Woener School
6131 LEONA ST, SAINT LOUIS, MO
6131 LEONA ST, SAINT LOUIS, MO
Owner
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101-1015
801 N 11TH ST, SAINT LOUIS, MO 63101-1015
Billing
Attn: Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601-0423
PO BOX 423, CHILLICOTHE, MO 64601-0423
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 6/4/2026 |
| conversion | conversion | n/a | No | No | Machine room door shall be self-locking. | 6/4/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | The in car stop switch has a broken mounting bezel. The stop switch shall be repaired. | 6/21/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 9/2/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The relief pressure shall be tested. | 9/2/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | The door closing force shall be tested. | 6/4/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 11/3/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operable | 5/23/2024 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | Yes | Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required. | 8/14/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | Yes | Yes | Upon re-inspection, found control valve had been replaced without alteration permit being issued. Elevator still dropped 1 3/4" during three 15 minute standing tests with shut off valve closed. Oil level in tank remained unchanged each time. Left unit Red-tagged. Re-inspection required | |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required. |