Inspection
Inspection Details
Equipment ID
16909
16909
Inspection Date
10/13/2021
10/13/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
17946e14-e210-47f8-820c-48f58c77fddc
17946e14-e210-47f8-820c-48f58c77fddc
Location
The Garden @ Renaissance
3117 Thomas St, St. Louis, MO
Phone: (314) 652-8900
3117 Thomas St, St. Louis, MO
Phone: (314) 652-8900
Owner
Attn: McCormack, Baron Ragan
McCormack, Baron Ragan
3217 Martin Luther King Dr, St. Louis, MO 63101
Phone: (314) 652-8900
Email: renaissancegardens@mccormackbaron.com
McCormack, Baron Ragan
3217 Martin Luther King Dr, St. Louis, MO 63101
Phone: (314) 652-8900
Email: renaissancegardens@mccormackbaron.com
Billing
Attn: Senior Livings & Gardens @ Renaissance
Senior Livings & Gardens @ Renaissance
3217 Martin Luther King Dr, St. Louis, MO 63106
Phone: (314) 652-8900
Email: Teneshea.Harvey@McCormackBaron.com
Senior Livings & Gardens @ Renaissance
3217 Martin Luther King Dr, St. Louis, MO 63106
Phone: (314) 652-8900
Email: Teneshea.Harvey@McCormackBaron.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Replace damaged fire service signage in car. | 4/18/2019 | ||
conversion | conversion | n/a | Pit light shall work. | 4/18/2019 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/24/2025 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The auxiliary battery lowering shall be operational. | 11/16/2022 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed) | 3/24/2025 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 9/27/2023 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | x | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 9/27/2023 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State operating certificate in machine room. | 3/24/2025 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Provide current tested fire extinguisher in machine room. | 3/24/2025 | ||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Machine room lighting shall properly operate. | 3/24/2025 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Up-to-date operating certificate required in the machine room. | 3/24/2025 | ||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Machine room lights shall work. | 3/24/2025 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 2/13/2025 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | x | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 2/13/2025 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/24/2025 | ||
A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | Repair hole in machine room ceiling. | 3/24/2025 | ||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Repair machine room lighting. | 3/24/2025 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Battery lowering does not work or have batteries. Battery lowering shall be operational and the disconnect shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. Note: This is the final notice for this violation. Failure to correct the violation will result in the elevator being red tagged and locked out of service. |