Inspection
Inspection Details
Equipment ID
25112
25112
Inspection Date
12/10/2021
12/10/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
90acbdd8-266f-484d-9aec-7596a854d360
90acbdd8-266f-484d-9aec-7596a854d360
Location
Chroma II
900 S Sarah St, St. Louis, MO
Phone: (000) 000-0000
Email: kelly.bigsby@kone.com
900 S Sarah St, St. Louis, MO
Phone: (000) 000-0000
Email: kelly.bigsby@kone.com
Owner
Attn: Green Street
Green Street Building Group
8451 Maryland Ave, Clayton, MO 63105
Phone: (000) 000-0000
Email: accountspayable@kdgi.com
Green Street Building Group
8451 Maryland Ave, Clayton, MO 63105
Phone: (000) 000-0000
Email: accountspayable@kdgi.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) | Yes | No | The in car emergency telephone shall be operational. | 11/25/2020 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.10.2.2.3(r) | Yes | No | Install hoistway and car top duct covers. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | The electrical disconnects shall be labeled with the location, name, and breaker numbers of the panel from which it is fed. | 11/25/2020 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | Governor rope shall not rub guard. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Yes | No | Provide code compliant onsite documents. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Provide a code compliant fire extinguisher near the machine space. | 11/25/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Test Phases 1 & 2 fire service and all fire service initiating devices. | 11/25/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Yes | No | Provide "In Case of Fire" signage. | 11/25/2020 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.11.10.1 | Yes | No | 2.11.10.1.1 - Provide landing sill guards. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.10.2.2.2(ll) | Yes | No | 8.10.1.1.4 - Provide acceptance test tags. | 11/25/2020 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Battery lowering shall be operational. | 11/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The suspension rope retainer on the drive sheave is rubbing the hoist ropes. Adjust for proper clearance. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |