Inspection
Inspection Details
Equipment ID
7123
7123
Inspection Date
12/9/2021
12/9/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
328640f7-c1d1-48a8-846f-70fbcee74724
328640f7-c1d1-48a8-846f-70fbcee74724
Location
Gallery 515
515 Olive St, St. Louis, MO
Phone: (314) 241-5964
515 Olive St, St. Louis, MO
Phone: (314) 241-5964
Owner
Attn: Brandonview LLC
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: mgummels@stlluxury.com
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: mgummels@stlluxury.com
Billing
Attn: Brandonview LLC
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: gallery515@stlluxury.com
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: gallery515@stlluxury.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Provide a current inspected fire extinguisher in the machine room. | 2/4/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide code compliant machine room lighting. | 2/4/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Make machine room exhaust fans code compliant. | 2/4/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Provide code compliant pit lighting. | 2/4/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | Cab lighting shall be guarded. | 2/4/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | The in car lighting shall be guarded and the exposed wiring shall be covered. | 3/15/2022 | ||
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.10.2 | Illumination at Landing Sills: The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 fc. Note: Some lobbies are under construction, and not lighted. | 3/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | The buffers, pit channels, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background. | 3/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/15/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | The in car lighting shall be guarded and the exposed wiring shall be covered. | 7/8/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.1 | The identification number for each elevator shall be painted on, engraved, or securely attached adjacent to or on every elevator entrance at the designated level, and shall be a minimum of 3 inches in height. | 7/8/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | The in-car emergency lights shall be operational. | 12/14/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/8/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | The fire extinguisher in machine room is out of date. | 7/8/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Auxiliary lighting in car is not functional. | 12/9/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Audible signal in car is not functional. | 12/9/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor is not functioning. | 12/9/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Auxiliary lighting in car is not functional. (2nd Notice) | 12/17/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Audible signal in car is not functional. (2nd Notice) | 12/17/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/8/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor is not functioning. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | x | Current State operating certificate shall be displayed in the equipment room in a non-combustible frame. (previously cited re-inspection to enforece) | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | x | The building corridos shall be so lighted that the illumination at the landing sills, when an elevator in service, shall be not less than 10fc. (previously cited re-inspection to enforece) | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | x | Permanet electric lighting shall be provided in all machine rooms and machinery spaced. The illumication shall be not less than 19 foot-candles at the floor level in the primary machine room. (previously cited re-inspection to enforece) | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.3.2 | x | The buffers, governor tail sheave, and/or the compensating sheave assembly, which are visible from the pit access door shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to it's background. (previously cited re-inspection to enforce) | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | x | Pit shall be kept clean and dry. Remove access debris. Previous water penetration noted in pit asl well. (previously cited re-inspection to enforce) | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Pit lighting shall not be less than 10fc at the pit floor. Current light does not work and will not meet this minimum. (previously cited re-inspection to enforce) | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | x | The in car lighting shall be guarded and the exposed wiring shall be covered. (previously cited re-inspection to enforce) |