Inspection
Inspection Details
Equipment ID
5751
5751
Inspection Date
8/16/2018
8/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Paul Bartlett
Paul Bartlett
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
730459d9-e667-4d63-b59e-caa0e9b81476
730459d9-e667-4d63-b59e-caa0e9b81476
Location
JQH Arena
685 S JOHN Q HAMMONS PKWY, SPRINGFIELD, MO
685 S JOHN Q HAMMONS PKWY, SPRINGFIELD, MO
Owner
Missouri State University
901 S NATIONAL AVE, SPRINGFIELD, MO 65897-0001
901 S NATIONAL AVE, SPRINGFIELD, MO 65897-0001
Billing
Attn: Missouri State University
901 S NATIONAL AVE, SPRINGFIELD, MO 65897-0001
901 S NATIONAL AVE, SPRINGFIELD, MO 65897-0001
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | 2/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 2/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Water observed in pit | 2/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | Remove "access" switch in COP or install outside of hoistway switches | 2/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | 1/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 1/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Water observed in pit | 1/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | Remove "access" switch in COP or install outside of hoistway switches | 1/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | S(1) Phase 2 instructions faded/worn. Replace. | 8/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust upthrust roller bearings for proper clearance to door hanger track.( 3rd floor) | 10/31/2022 |