Inspection
Inspection Details
Equipment ID
10700
10700
Inspection Date
12/16/2021
12/16/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
29
29
External ID
7590f788-190e-4089-bd49-9b2d6e3481bf
7590f788-190e-4089-bd49-9b2d6e3481bf
Location
Parkview Elderly Apts
4451 Forest Park Ave, St. Louis, MO
Phone: (314) 533-3350
4451 Forest Park Ave, St. Louis, MO
Phone: (314) 533-3350
Owner
Attn: Parkview Elderly Apts
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 533-3350
Email: areeves@habitat.com
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 533-3350
Email: areeves@habitat.com
Billing
Attn: Andy Reeves
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: areeves@habitat.com
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: areeves@habitat.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pits shall be clean | 5/9/2019 |
| conversion | conversion | n/a | No | No | Emergency phone not working | 5/9/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lighting needs to be guarded. | 5/9/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor does not work. | 5/7/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean elevator pit. | 7/21/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diamter. | 5/12/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site for each elevator. | 6/15/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry & clean and free of equipment or material not relating to the operation of the elevator | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A MCP shall be provided for each unit and kept on site | 3/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator was not running at scheduled test date. Repair elevator and perform annual no load test of elevator. | 1/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator test needs to be witnessed when all Modernizations are completed. | 5/27/2025 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | After the third car modernization is finished, all covers on electrical boxes shall be installed. | 5/27/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | All cross wiring connections shall be complete. | 5/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Elevator cab must have a permanent slip resistant floor installed. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room door must be self-closing and self-locking | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power must be tested annually. |