Inspection
Inspection Details
Equipment ID
8654
8654
Inspection Date
12/15/2021
12/15/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
22
22
External ID
bc5e06f4-179b-46fd-8c1a-091931e89a70
bc5e06f4-179b-46fd-8c1a-091931e89a70
Location
Clayton Corporate Park Management Company
700 Corporate Park Dr, Clayton, MO
Phone: (000) 000-0000
700 Corporate Park Dr, Clayton, MO
Phone: (000) 000-0000
Owner
Clayton Corp Park Management Company
700 CORPORATE PARK DR, CLAYTON, MO 63105-4209
700 CORPORATE PARK DR, CLAYTON, MO 63105-4209
Billing
Attn: Clayton Corporate Park Management Co.
600 CORPORATE PARK DR, CLAYTON, MO 63105-4204
600 CORPORATE PARK DR, CLAYTON, MO 63105-4204
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 9/16/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | On the top of the elevator cab, the cab steadier bushings have degraded and require replacement. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The counterweight hitch end has a spring that is broken in the hoistway that shall be replaced for the hoisting ropes to have an equal amount of tension. | |||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. | 9/16/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | On the top of the elevator cab, the cab steadier bushings have degraded and require replacement. | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | The counterweight hitch end has a spring that is broken in the hoistway that shall be replaced for the hoisting ropes to have an equal amount of tension. | |||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase I key switches. Obtain the correct signage from the building cade addition that this elevator was designed to meet. | |||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Test rescue phone for all 3 units. Must be tested at the time of final modernization. | ||
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | x | Reinstall handrail on steps going into machine room. | ||
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Outlets shall be GFCI protected. | ||
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | x | Fill smoke penetrations with approved fire rated caulking. | ||
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | A proper fire extinguisher shall be provided. | ||
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Main and lighting disconnects shall have proper labeling for function and feeder locations. | ||
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Fill smoke penetrations with approved fire caulking/materials. | ||
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Install missing duct covers. | ||
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | x | 3rd floor door upthrusts shall be adjusted for proper clearance. | ||
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Double outlet in the pit shall be GFCI protected or removed. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | All FAID devices to be functionality tested at completion of #3 MOD inspection. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | x | All call stations in lobby must be permanently mounted. |