Inspection
Inspection Details
Equipment ID
18999
18999
Inspection Date
12/28/2021
12/28/2021
Inspection Type
Alteration
Alteration
Inspector Name
David Folkert
David Folkert
Mechanic Name
Paul Jaremko
Paul Jaremko
Relief Valve Pressure
Slide
7
7
Governor Rope Pull
460
460
Door Closing Force
Na
Na
External ID
1470a2a4-58b7-453a-a94c-e10054328064
1470a2a4-58b7-453a-a94c-e10054328064
Location
Iatan Station
20256 State Rte 45 N, Weston, MO
Phone: (816) 386-2047
Email: donald.hughes@evergy.com
20256 State Rte 45 N, Weston, MO
Phone: (816) 386-2047
Email: donald.hughes@evergy.com
Owner
Attn: Steven Thomas
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
Billing
Attn: William Bowen
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: william.bowen@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: william.bowen@evergy.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Alarm button does not actuate emergency alarm bell. | 1/17/2019 | ||
conversion | conversion | conversion - reinspect | x | Repair or replace governor to ensure that all moving parts operate freely. | 6/1/2018 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Provide code data plate on disconnect or controller | 9/16/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Elevator does not recall to fire designated landing when phase 1 key switch is activated to on position. | 12/28/2021 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | x | x | Governor tripping speed exceeds maximum allowable tripping speed. Governor linkage is corroded. | 12/28/2021 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | x | Brake will not stop and hold 125% of rated load. Brake linkage can not be adjusted due to chemical corrosion. Brake linkage needs replacement. | 12/28/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 8.11.2.3.1 | x | x | Need to perform safety test with rated load on the car | 12/28/2021 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Machine room door does not open from inside machine room. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Provide new pit ladder. Existing pit ladder is rusted through. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Bottom landing sill to be maintained flush and level with floor surface of landing | 12/28/2021 | |
A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.4 | x | Install a seal on brake tension adjustment along with a metal tag identifying the firm that installed the seal. | 12/28/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Elevator does not recall to designated landing when phase 1 keyswitch is keyed to on. | |
A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.1 | x | Provide ascending car overspeed protection | ||
A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | x | Provide unintended car movement protection. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Provide firefighter phase 2 operation panel cabinet on car operating panel | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Hoistway access switches do not function | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Test and log firefighter operation monthly | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No maintenance records on site | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Bottom landing entrance sill is not flush with landing floor. Fill 1 inch gap between landing and entrance sill | |||
A17.1-2016 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service | x | x | Elevator has been decommissioned |