Inspection
Inspection Details
Equipment ID
13090
13090
Inspection Date
11/30/2021
11/30/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
8"
8"
Governor Rope Pull
160/600
160/600
Door Closing Force
24F/26R
24F/26R
External ID
161e4291-d239-4086-8bfb-b7906b5ef63b
161e4291-d239-4086-8bfb-b7906b5ef63b
Location
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO
Phone: (314) 621-5848
200 S Tucker Blvd, St. Louis, MO
Phone: (314) 621-5848
Owner
Attn: Emma Harris
St. Louis City Justice Center
200 S TUCKER BLVD, SAINT LOUIS, MO 63102
Phone: (314) 621-5848
Email: harrise@stlouis-mo.gov
St. Louis City Justice Center
200 S TUCKER BLVD, SAINT LOUIS, MO 63102
Phone: (314) 621-5848
Email: harrise@stlouis-mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | No current state certificate posted. | 7/8/2018 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certiicate in machine room | 3/18/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current MO state operating certificate. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including on-site documents. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Standby power operation of the elevators shall be tested. | 4/8/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Properly display current state operating certificate in the machine room. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service testing records are missing. (This item is for notification purposes for future violation in 2022) | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way emergency communication shall be operational. | 12/5/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work with and without main power. | 11/19/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. Note: Elevator failed to operate on emergency generator. | 11/19/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 2023 documentation is blank and no fire service logs present. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tags. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work with and without main power. (2nd Notice) This violation must be corrected immediately. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |