Inspection
Inspection Details
Equipment ID
11772
11772
Inspection Date
9/14/2017
9/14/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
Location
Vashon High School
3035 Cass Ave, St. Louis, MO
Phone: (314) 231-3720
3035 Cass Ave, St. Louis, MO
Phone: (314) 231-3720
Owner
St. Louis Board of Education
801 N. 11th Street, St. Louis, MO 63101
801 N. 11th Street, St. Louis, MO 63101
Billing
Attn: Advanced Elevator
PO Box 423, , MO 64601
PO Box 423, , MO 64601
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room lights are controlled by a motion sensor not located in the machine room. | 9/9/2019 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Make machine room lights operational from switch in the machine room. | 9/9/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Yes | No | The pit shall be kept clean and dry. | 8/1/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room shall not be used for the storage of non-elevator related items. | 9/9/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/17/2022 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 10/17/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 11/10/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 5/4/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on emergency backup power. Re-inspection required | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room is not to be used for a storage closet, elevator related items only |