Inspection
Inspection Details
Equipment ID
13092
13092
Inspection Date
12/2/2021
12/2/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
382e06f8-c742-4548-9ae2-06f624b5f4fd
382e06f8-c742-4548-9ae2-06f624b5f4fd
Location
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO
Phone: (314) 621-5848
200 S Tucker Blvd, St. Louis, MO
Phone: (314) 621-5848
Owner
Attn: Emma Harris
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO 63102
Phone: (314) 621-5848
Email: harrise@stlouis-mo.gov
St. Louis City Justice Center
200 S Tucker Blvd, St. Louis, MO 63102
Phone: (314) 621-5848
Email: harrise@stlouis-mo.gov
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Elevator has more than 1 compartment. | 7/20/2018 | ||
conversion | conversion | n/a | No current state certificate posted. | 7/20/2018 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State certificate in machine room | 10/17/2019 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Repair means of two way communications with car | 10/1/2019 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display a current MO state operating certificate. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide a code compliant MCP including on-site documents. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency communication device shall be operational. | 4/8/2021 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Standby power operation of the elevators shall be tested. | 4/8/2021 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Properly display current state operating certificate in the machine room. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service testing records are missing. (This item is for notification purposes for future violation in 2022) | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way emergency communication shall be operational. | 12/6/2022 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/8/2023 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication device shall work with and without main power. | 11/19/2024 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Emergency power jewel does not illuminate. Take corrective action as needed. Note: Emergency power operation did work. | 11/19/2024 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 2023 documentation is blank and no fire service log is present. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication device shall work with and without main power. (2nd Notice) This violation must be corrected immediately. | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |