Inspection
Inspection Details
Equipment ID
11874
11874
Inspection Date
12/28/2021
12/28/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
4ce7fbb6-730d-49ae-b064-434d9b19b0c6
4ce7fbb6-730d-49ae-b064-434d9b19b0c6
Location
The Dorchester
665 S Skinker Blvd, St. Louis, MO
Phone: (314) 721-8181
665 S Skinker Blvd, St. Louis, MO
Phone: (314) 721-8181
Owner
Attn: The Dorchester
The Dorchester
665 S Skinker Blvd, St. Louis, MO 63105
Phone: (000) 000-0000
Email: kbozoian@macapartments.com
The Dorchester
665 S Skinker Blvd, St. Louis, MO 63105
Phone: (000) 000-0000
Email: kbozoian@macapartments.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Replace the missing machine room door knob. Must be self-locking type. | 2/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 2/6/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher in the machine room is expired and shall be replace or serviced. | 2/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | The machine room vent shall be provided with a cover. | 2/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | No | No | Seal all machine room penetrations. | 2/28/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 1/5/2022 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 1/5/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone does not work. Initiate the necessary corrective action. | 12/28/2021 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. Relocate security system from machine room. | 2/3/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in machine room. | 2/3/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Main COP ADA/Help phone is not working. AUX COP handset phone does work. Where emergency phones are provided they shall be operational. | 2/23/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP, including PM records and monthly fire service test log, not being properly documented. | 2/28/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Front pit sump pump appears to not be working. | 2/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing/damaged pickup rollers. | 2/28/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 2/28/2024 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 111 | No | No | Hoistway doors at floor one need to be adjusted/repaired. Gap approximately 2.5". (Bi-parting freight doors) | 2/28/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. 2022 MCP records are missing. | 2/28/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Unit is now out of service per CSR40-5.090 Inspection and Testing Section 8.11.1.4(b)(2). Red Tag applied to disconnect. |