Inspection
Inspection Details
Equipment ID
16940
16940
Inspection Date
7/16/2018
7/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wendy Eiss
Wendy Eiss
Mechanic Name
Ricky Wolf
Ricky Wolf
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
2649707f-4858-4174-b0ff-736743d994dc
2649707f-4858-4174-b0ff-736743d994dc
Location
Ann Hawkins Gentry Middle School
4200 BETHEL ST, COLUMBIA, MO
4200 BETHEL ST, COLUMBIA, MO
Owner
Columbia Public Schools
1818 W WORLEY ST, COLUMBIA, MO 65203-1038
1818 W WORLEY ST, COLUMBIA, MO 65203-1038
Billing
Attn: Columbia Public Schools
1818 W WORLEY ST, COLUMBIA, MO 65203-1038
1818 W WORLEY ST, COLUMBIA, MO 65203-1038
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency lights are inoperable. | 9/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Only one bulb working for normal lighting. Ceiling panels need to be installed. | 9/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone must have correct # | 6/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room needs fire extinguisher | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs location information for contact | 7/17/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room needs fire extinguisher | 12/21/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Oil on floor needs cleaning | 12/21/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Twin post jacks repacked. Oil and mess needs cleaned up | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | PIT HAS OIL STILL IN THE PIT MUST FIND SOURCE AND CLEAN PIT | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | MUST ADD CLEAR OIL COLLECTION BUCKETS | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Yes | No | BACK WALL NEEDS BE SECUED TO THE FLOOR | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Yes | No | MUST REPLACE FLOORING THAT IS MISSING |