Inspection
Inspection Details
Equipment ID
4227
4227
Inspection Date
12/2/2021
12/2/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Ralph Kinnison
Ralph Kinnison
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
0e9e996e-4b54-4625-a7e4-296d0a427dab
0e9e996e-4b54-4625-a7e4-296d0a427dab
Location
Truman Farm Villa Apt
5306 Harry S Truman Dr, Grandview, MO
Phone: (816) 966-0500
5306 Harry S Truman Dr, Grandview, MO
Phone: (816) 966-0500
Owner
Attn: Peak Living Truman Farm Villas
Peak Living Truman Farm Villas
2174 W Grove Pkwy, Ste 100, Pleasant Grove, UT 84062
Phone: (385) 375-3255
Email: trumanfarmcm@peakliving.com
Peak Living Truman Farm Villas
2174 W Grove Pkwy, Ste 100, Pleasant Grove, UT 84062
Phone: (385) 375-3255
Email: trumanfarmcm@peakliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | replace missing hoistway pick up rollers on the middle landing | 2/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | replace the emergency light battery | 1/30/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post the log in the machine room | 2/19/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean up pit, oil in pit, pit can overflowing | 2/19/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | replace the cylinder packing, pit can overflows between service visits | 2/19/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Building lost power just as we were starting the inspection, schedule reinspection when building power has been restored | 1/26/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post a new copy of the state Certificate in the machine room every year | 2/19/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light does not work, replace light bulb | 2/19/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | fire service is not working, turned the phase 1 keyswitch and nothing happened. | 2/1/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | machine room light is burnt out, replace bulb | 1/27/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not posted in the machine room, perform fire service test monthly and keep a test log in the machine room | 1/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone line is dead, provide working phone line | 12/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 3/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting below 10 foot candles | 3/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher out of date | 3/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs cleaning | 3/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump hole needs cover | 3/7/2024 |