Inspection
Inspection Details
Equipment ID
19103
19103
Inspection Date
1/11/2022
1/11/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
341c7251-ca97-4b1d-bdfd-af7981705398
341c7251-ca97-4b1d-bdfd-af7981705398
Location
P T Bosley Senior Estates
4301 Warne Ave, St. Louis, MO
Phone: (314) 534-4700
4301 Warne Ave, St. Louis, MO
Phone: (314) 534-4700
Owner
Attn: Priscilla Redd-Brown
P T Bosley Senior Estates
4301 Warne Ave, St. Louis, MO 63107
Phone: (314) 534-4700
Email: predd-brown@voa.org
P T Bosley Senior Estates
4301 Warne Ave, St. Louis, MO 63107
Phone: (314) 534-4700
Email: predd-brown@voa.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 210.1a | No | No | Replace missing stop switch in car operating panel | 2/8/2023 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | Adjust car door operator excessive force | 2/8/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Door restricter not working | 2/24/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Need to include testing procedures in the MCP on or before 1/1/22 | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working | 12/21/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | On phase 1 recall door clos button does not work unable to test phase 2, ?Red tagged out of service | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.1 Means of Communication (Red Tag) | No | No | Emergency phone still not working | 1/11/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 1/9/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car. Reinspection required within 30 days | 3/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair Phone in the Car |