Inspection
Inspection Details
Equipment ID
3625
3625
Inspection Date
1/12/2022
1/12/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Melvin Barks Jr.
Melvin Barks Jr.
Mechanic Name
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
17ee7e3a-213e-4157-8900-1d15a44b1dff
17ee7e3a-213e-4157-8900-1d15a44b1dff
Location
Messenger Towers
102 E 2nd St, Joplin, MO
Phone: (417) 624-1118
Alt Phone: (417) 437-0672
102 E 2nd St, Joplin, MO
Phone: (417) 624-1118
Alt Phone: (417) 437-0672
Owner
Attn: Dominium Management Services
Dominium Management Services
2905 Northwest Blvd, Ste 150, Plymouth, MN 55441
Phone: (314) 492-3994
Email: jenni.feder@dominiuminc.com
Dominium Management Services
2905 Northwest Blvd, Ste 150, Plymouth, MN 55441
Phone: (314) 492-3994
Email: jenni.feder@dominiuminc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 1.6 telephone will not work | 2/27/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | telephone needs replaced will not call | 5/4/2020 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed | 1/12/2022 |
| A17.1-2016 : Elevators | 3.27 - Crosshead Data Plate and Rope Data Tags | 8.11.2.1.3(k) | No | No | No hoist rope tags | 7/29/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove dirt and rubbish from pit floor | 7/29/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room requires housekeeping | 7/29/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Provide cover on 4X4 box | 7/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Phase one key switch jewel not readable | 7/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide mcp in machine room | 7/29/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove dirt and rubbish from pit floor | 7/29/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate | 7/29/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | provide operational telephone | 3/28/2025 |