Inspection
Inspection Details
Equipment ID
20327
20327
Inspection Date
1/4/2022
1/4/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
22defc74-27d8-40eb-8fce-51c63b4d534a
22defc74-27d8-40eb-8fce-51c63b4d534a
Location
Temtor Lofts
8125 MICHIGAN AVE, SAINT LOUIS, MO
Phone: (314) 322-1037
8125 MICHIGAN AVE, SAINT LOUIS, MO
Phone: (314) 322-1037
Owner
Attn: Temtor Group LLC
Temtor Group LLC
2654 Gravois Ave, St. Louis, MO 63118
Phone: (314) 322-1037
Email: rent@stlresociety.com
Temtor Group LLC
2654 Gravois Ave, St. Louis, MO 63118
Phone: (314) 322-1037
Email: rent@stlresociety.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. The displayed certificate is expired. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation and the date shall be available on-site. The monthly log is in the MCP, but is not being filled out. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit light switch shall be operational. The pit light switch shall be maintained in the on or off position when released. It presently returns to the off position when released. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway Door Safety Retainers/Fire tabs shall be installed at the bottom of all hoistway doors. | 3/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | 3/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. | 3/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Clean hoistway. Excessive hair/debris on doors, brackets, etc. Fire hazard. | 3/15/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | 2.20.9.4 - Hoist rope tail retaining clips shall be properly spaced. Also, some clips are missing. | 3/15/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The car went down during the inspection, testing incomplete. The following items still need to be tested: Fire service shall be tested and pit shall be checked. | 3/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | Yes | No | Lockable access door at bottom of car operating panel, which secures attendant operation switches is broken off hinges and shall be permanently repaired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maitenance records shall document compliance with 8.6 of the code, including testing of firefighters service. |