Inspection
Inspection Details
Equipment ID
5732
5732
Inspection Date
1/12/2022
1/12/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Harris
David Harris
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
28d93d4d-bb21-4425-ba24-e71473fbd38c
28d93d4d-bb21-4425-ba24-e71473fbd38c
Location
Reeves Library
501 Westminster Ave, Fulton, MO
Phone: (573) 592-5282
501 Westminster Ave, Fulton, MO
Phone: (573) 592-5282
Owner
Attn: Westminster College
Westminster College
501 Westminster Ave, Fulton, MO 65251
Phone: (000) 000-0000
Email: diane.hammerstone@westminster-mo.edu
Westminster College
501 Westminster Ave, Fulton, MO 65251
Phone: (000) 000-0000
Email: diane.hammerstone@westminster-mo.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 3/6/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. There is no MCP in the machine room. | 3/6/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. The written record shall be kept in the machine room. | 3/6/2026 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/6/2026 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 3/6/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The in car alarm bell shall be operational on auxiliary power. | 10/30/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 10/30/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The in car emergency lights shall be operational. | 10/30/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. (2nd Notice) This violation originally cited on 2/6/2024 has still not been corrected. This violation must be corrected immediately or unit may be locked out of service and red tagged. | 3/3/2025 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Machine room has 2 inches of water that shall be removed. Correct source of leak. | 3/6/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Wiring diagrams shall be provided in the elevator machine room. | 3/6/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The in car emergency lighting shall be operational. | 3/6/2026 |