Inspection
Inspection Details
Equipment ID
13588
13588
Inspection Date
1/13/2022
1/13/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Ross Colligan
Ross Colligan
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
9e4b87cb-eff7-4215-83fa-3519cc67e21a
9e4b87cb-eff7-4215-83fa-3519cc67e21a
Location
All-Type Containers
1400 Collins St, St. Louis, MO
Phone: (314) 621-0222
1400 Collins St, St. Louis, MO
Phone: (314) 621-0222
Owner
Attn: Veni Vidi Vici LLC
Veni Vidi Vici LLC
PO Box 111, Fenton, MO 63026
Phone: (000) 000-0000
Veni Vidi Vici LLC
PO Box 111, Fenton, MO 63026
Phone: (000) 000-0000
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Spin out cables are missing on both car and counterweights. | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. | 11/30/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Needs guard over lights on car top. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Lighting in machine room not adequate. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No maintenance records on site. | |||
MO Minimum : Elevators | (A) - Hoistways | (A)10 | Repair access pull chain at the top floor. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Emergency light and bell are not working on battery back-up. | 11/30/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Missing spin out cables on both car & counterweights | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No maintenance records on site | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in machine room is not adequate | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | There is no emergency phone, just wires for the phone | 1/13/2022 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | No alarm bell | 1/13/2022 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Cab lighting needs guards to cover them | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | x | Emergency light & alarm bell does not work | 1/13/2022 |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | There needs to be an up to date fire extinguisher in the machine room | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door needs to be self closing & locking | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Ladder up to machine room needs to be addressed, not permanently attached, has broken rungs | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No maintenance records on site | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door needs to be self closing/locking |