Inspection
Inspection Details
Equipment ID
6664
6664
Inspection Date
7/13/2018
7/13/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
13
13
External ID
693390a4-e6d6-4173-ab0c-4bd54c19884b
693390a4-e6d6-4173-ab0c-4bd54c19884b
Location
Ariel Premium Supply Inc
8825 PAGE AVE, SAINT LOUIS, MO
8825 PAGE AVE, SAINT LOUIS, MO
Owner
Premium Supply Inc
8530 PAGE AVE, SAINT LOUIS, MO 63114-6016
8530 PAGE AVE, SAINT LOUIS, MO 63114-6016
Billing
Attn: Ariel Premium
8825 PAGE AVE, SAINT LOUIS, MO 63114-6105
8825 PAGE AVE, SAINT LOUIS, MO 63114-6105
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Note: Only wiring diagrams are on-site. | 7/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The door re-opening photo eyes do not work. | 3/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-locking. | 7/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab lighting shall be a minimum of 5 foot-candles. | 7/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lighting shall be a minimum of 5 ftc. | 7/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door reopening photo eye does not work. (2nd Notice) | 7/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. | 7/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 7/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | Drain line from jack goes into a tank. It must go into maximum 5 gal bucket for proper monitoring per MO Memorandum 006. | 3/25/2025 |