Inspection
Inspection Details
Equipment ID
6364
6364
Inspection Date
8/16/2018
8/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Richard Dalman
Richard Dalman
Relief Valve Pressure
Slide
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
3633df15-e553-4f09-87d4-e1750238a89e
3633df15-e553-4f09-87d4-e1750238a89e
Location
Corby Building
422 FELIX ST, SAINT JOSEPH, MO
422 FELIX ST, SAINT JOSEPH, MO
Owner
Corby Senior Living
PO BOX 374, PICO RIVERA, CA 90660-0374
PO BOX 374, PICO RIVERA, CA 90660-0374
Billing
Attn: Corby Senior Living
PO BOX 374, PICO RIVERA, CA 90660-0374
PO BOX 374, PICO RIVERA, CA 90660-0374
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light and bell do not operate. | 12/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Need to post fire service instructions inside the elevator | 12/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Need to remove debris from machine room floor. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need to post emergency evacuation of passengers form inside machine room. | 8/25/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace rouged and undersized governor rope. | 7/16/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties do not stop the elevator. Slide is 56 inches and exceeds allowed limits | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Install seal on machine brake spring tension adjustment nut. | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn traction sheave liners | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace broken hoist rope shackle springs on the car and counterweight connections | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Equalize hoist rope tension | 12/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Lobby dial position indicator is not operating and needs repair. | 12/7/2023 |