Inspection
Inspection Details
Equipment ID
13869
13869
Inspection Date
1/24/2022
1/24/2022
Inspection Type
Alteration
Alteration
Inspector Name
Wayne Coder
Wayne Coder
Mechanic Name
Tim Switzer
Tim Switzer
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
22F/22R
22F/22R
External ID
dbf5cdcd-3896-4f95-829b-02f47193f1aa
dbf5cdcd-3896-4f95-829b-02f47193f1aa
Location
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
777 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
Owner
Attn: John Koshinski
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | No current MO state operating certificate in the elevator machine room. | |
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell does not work | 8/9/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Rear car door restrictor does not work | 8/9/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency lights do not work | 8/9/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Gap between lower hoistway door and jam is over 3/8 has 1inch gap | 8/9/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | replace rusted conduit in machine room | 8/9/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work with power off. | 5/16/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Repair or replace cartop exit switch. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Need battery for emergency phone. | 9/9/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Remove corrosion from supply pipe that leads from machine room to pit. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Cover exposed wiring, due to corrosion, in machine room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed needs a full load test. Perform load test and check tripping speeds within 90 days or less. (11-10-21) REINSPECT | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit is full of water. Remove water and debris | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator cab does not work. Repair | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Enclose exposed electrical wiring on car top door reopening control box |