Inspection
Inspection Details
Equipment ID
12585
12585
Inspection Date
1/27/2022
1/27/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
a1e5b095-8241-4aff-8ec2-47f6dacef467
a1e5b095-8241-4aff-8ec2-47f6dacef467
Location
Continental Life Bldg
3615 Olive St, St. Louis, MO
Phone: (314) 802-8840
3615 Olive St, St. Louis, MO
Phone: (314) 802-8840
Owner
Attn: Continental Life Bldg c/o Sansone Group
Continental Life Bldg c/o Sansone Group
120 S Central Ave, Ste 500, Saint Louis, MO 63105
Phone: (314) 336-3368
Email: nhammett@sansonegroup.com
Continental Life Bldg c/o Sansone Group
120 S Central Ave, Ste 500, Saint Louis, MO 63105
Phone: (314) 336-3368
Email: nhammett@sansonegroup.com
Billing
Attn: Continental Life Bldg
Continental Life Bldg
3615 Olive Street, St. Louis, MO 63103
Phone: (314) 336-3368 Ext: 368
Email: kdurrwachter@sansonegroup.com
Continental Life Bldg
3615 Olive Street, St. Louis, MO 63103
Phone: (314) 336-3368 Ext: 368
Email: kdurrwachter@sansonegroup.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable alarm bell. | 7/10/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Repair inoperative door restrictor. | 2/19/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Replace missing door gibbs 21st and 7th floors | 5/12/2021 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Replace defective hoist cables due to heavy rouge and diameter reduction by 1/20/20 | 2/19/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Fire recall buzzer inoperative. | 4/23/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/23/2021 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Replamp machine room lighting fixtures above machines. | 5/12/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Need light above controller | 1/27/2022 |
| A17.1-2016 : Elevators | 1.12 - Car enclosure | 8.11.2.1.1(l) | No | No | Iron on cab walls needs to be secured | 1/27/2022 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | Fire tabs on door hangers | 1/27/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Dust covers in machine room | 1/27/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed live wiring on brake switches | 1/27/2022 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.11.2.1.2(ff) | Yes | Yes | Govenor test failed, Red tagged elevator | 1/27/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vison plate over it. | 12/31/2024 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | Yes | No | Upper hoistway door hanger safety retainers are defeated/turned down on almost all doors. Shall be corrected. (Previously Cited Violation) | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby, 1.5", does not meet Code Requirements. Shorten cables | |
| A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.5 | No | No | COP shall have car number displayed, 0.5" lettering. | |
| A17.1-1996 : Elevators | 3.27 - Crosshead data plate | 212.2 | No | No | Suspension ropes shall have proper data tag(s) | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris |