Inspection
Inspection Details
Equipment ID
15889
15889
Inspection Date
7/23/2018
7/23/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
610
610
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
167db147-78c0-4599-b8ab-9e031033821b
167db147-78c0-4599-b8ab-9e031033821b
Location
Emerson Electric/W Building
8100 FLORISSANT RD, SAINT LOUIS, MO
8100 FLORISSANT RD, SAINT LOUIS, MO
Owner
Emerson Electric
8000 W FLORISSANT AVE, SAINT LOUIS, MO 63136-1414
8000 W FLORISSANT AVE, SAINT LOUIS, MO 63136-1414
Billing
Attn: DCM Group
8300 EAGER RD STE 601, SAINT LOUIS, MO 63144-1419
8300 EAGER RD STE 601, SAINT LOUIS, MO 63144-1419
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not working. Re-inspection required | 8/1/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 8/1/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Drop ceiling panels are open egg crate type, which provides no protection for passengers in event of bulb breakage. Replace with solid panels or install plastic tubes and end caps over bulbs | 8/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state operating certificate shall be displayed in elevator machine room | 8/1/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 9/24/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 9/24/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Drop ceiling panels are open egg crate type, which provides no protection for passengers in event of bulb breakage. Replace with solid panels or install plastic tubes and end caps over bulbs. (noted on previous report) | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Battery lowering device inoperable, repair or replace as needed. | 3/27/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Battery lowering device inoperable, needs repaired or replaced. Re-inspection required | 7/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Battery lowering device inoperable, repair or replace as needed. 8.6.4.19.7 | 3/3/2026 |