Inspection
Inspection Details
Equipment ID
16584
16584
Inspection Date
1/31/2022
1/31/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Jeremiah Dugger
Jeremiah Dugger
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
de4dcfe7-3eb9-4386-b424-c437db04439a
de4dcfe7-3eb9-4386-b424-c437db04439a
Location
Q-Hotel
1117 E Saint Louis St, Springfield, MO
Phone: (417) 864-4300
1117 E Saint Louis St, Springfield, MO
Phone: (417) 864-4300
Owner
Attn: Paul
Atrium Hospitality
300 S John Q Hammons Pkwy H#JQ, Springfield, MO 65806
Phone: (417) 862-0070
Email: david.wheeler@atriumhospitality.com
Atrium Hospitality
300 S John Q Hammons Pkwy H#JQ, Springfield, MO 65806
Phone: (417) 862-0070
Email: david.wheeler@atriumhospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Replace the missing door closer on machine room door.it is to be self closing self latching. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Replace the emergency light battery as it is dead | 1/31/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Replace the burnt up sump pump and remove the plywood cover you placed over the pit it has to be metal and it is laying in the pit. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as there is no dial tone. | 4/11/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Replace the emergency light battery. | 4/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Re-install the missing fire damper in the HVAC VENT pipe on the machine room ceiling. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Have the fire extinguisher re-certified | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Have the emergency phone repaired as it has no dial tone | 2/6/2025 |