Inspection
Inspection Details
Equipment ID
19533
19533
Inspection Date
1/17/2022
1/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Jasen Kennedy
Jasen Kennedy
Relief Valve Pressure
620
620
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
d087142e-81f5-4c9c-8ac7-377ee757f633
d087142e-81f5-4c9c-8ac7-377ee757f633
Location
Creekside Village Condo
901-933 NE Deer Creek Dr, Grain Valley, MO
Phone: (816) 228-9667
901-933 NE Deer Creek Dr, Grain Valley, MO
Phone: (816) 228-9667
Owner
Attn: Creek Side Real Estate
Creekside Real Estate LLC
14793 Vickery Ave, Saratoga, CA 95070
Phone: (816) 224-7911
Creekside Real Estate LLC
14793 Vickery Ave, Saratoga, CA 95070
Phone: (816) 224-7911
Billing
Attn: CJ Real Estate, Inc
CJ Real Estate, Inc
1850 NW State Route 7, Blue Springs, MO 64014
Phone: (816) 224-7911 Ext: 124
Email: Landerson@cjproperties.org
CJ Real Estate, Inc
1850 NW State Route 7, Blue Springs, MO 64014
Phone: (816) 224-7911 Ext: 124
Email: Landerson@cjproperties.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | fire service test log is to be filled out monthly, currently only filled out quarterly | 3/9/2020 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.11.3.1.1(e) | No | No | replace cab ceiling light bulbs that are burnt out | 2/16/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | the monthly fire service test log is not being filled out | 2/16/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the state operating certificate is to be posted in the elevator machine room | 2/16/2021 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 8.11.3.1.2(b) | No | No | machine room door will not lock, the door jamb hole for the lock does not line up with the locking mechanism on the door | 2/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | did not have current maintenance log in the machine room | 3/1/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service log is not being filled out | 3/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | only das one working light bulb in the elevator cab, required to have two working light bulbs | 5/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room fire extinguisher was last inspected in 2022, have the fire extinguisher inspected annually | 3/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not work. No dial Town on the phone line provide working phone line. | 2/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not work, no power on the phone line | 4/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | No | No | Mark the location of the feeder circuits for the main line and 110 discount in the machine room with the panel and breaker number they are fed from | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Monthly fire service log is not being filled out, fill out monthly fire service log with date and year that the test were performed | 3/31/2026 |
| A17.1-2016 : Elevators | 5.13 - Guiding Members | 3.15.1 | No | No | Replace worn out slide guides (3.15.1.1.2) | 3/31/2026 |