Inspection
Inspection Details
Equipment ID
12769
12769
Inspection Date
11/17/2021
11/17/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Ronnie Ritch
Ronnie Ritch
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
26362cd5-a3bc-49a2-862e-62b0b19923c2
26362cd5-a3bc-49a2-862e-62b0b19923c2
Location
McCormack House
4575 Cadet Ave, St. Louiis, MO
Phone: (314) 371-2525
4575 Cadet Ave, St. Louiis, MO
Phone: (314) 371-2525
Owner
Attn: McCormack House
McCormack House
4575 Cadet Ave, St. Louis, MO 63110
Phone: (000) 000-0000
Email: Brionna.Ivie@McCormackBaron.com
McCormack House
4575 Cadet Ave, St. Louis, MO 63110
Phone: (000) 000-0000
Email: Brionna.Ivie@McCormackBaron.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Electric eyes are not working. | 9/19/2019 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Door re-opening device shall work. | 9/19/2019 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Remove non-electrical material from machine space. | 9/19/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light shall work. | 12/10/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell shall work. | 12/10/2019 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed or tagged, notified on last visit, must be sealed & tagged within 90 days. | 5/27/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris in pit | 5/27/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting in-operable | 5/27/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 6/14/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris in pit | 8/4/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting inoperable. | 8/4/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | reinspection of elelvator phone. Still nto working. Repair phone. Reinspect by 7/14/23 (30 days) | 7/13/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Reinspection of debris in elelvator pit. Still dirty. Clean elevator pit. | 8/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Reinspection fo elelvator pit lights. Still not working. Repair lights. | 8/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Re-inspection of elevator pit lights, still not working. Need to repair pit lights | 7/13/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency battery lowering device does not work, needs repaired. Re-inspection required |