Inspection
Inspection Details
Equipment ID
15155
15155
Inspection Date
1/10/2022
1/10/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
f709207f-892a-4f52-b479-cf01d1842cec
f709207f-892a-4f52-b479-cf01d1842cec
Location
Plaza Square- Bldg 40
40 Plaza Sq, St. Louis, MO
Phone: (314) 565-7023
40 Plaza Sq, St. Louis, MO
Phone: (314) 565-7023
Owner
Attn: Mills Properties Inc Cityview Apartments
Mills Properties Inc Cityview Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Mills Properties Inc Cityview Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The hoist ropes need replacing. | 1/6/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.1.5(j) | Yes | Yes | A category 5 full load test shall be witnessed. | 1/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | Yes | Passenger elevators shall safely lower, stop, and hold the car with an additional load up to 125% in excess of the rated load. The machine brake would no hold the rated load. Unit Red Tagged. | 1/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.1.5(j) | Yes | Yes | A category 5 full load test shall be witnessed. Could not witness full load on 1/14/2020 due to machine brake failure. | 1/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 5/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | A suspension rope tag shall be installed as specified by A17.1 2005 - 2.20.2.2 | 5/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 2/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures are missing from the MCP. | 2/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in the machine room in a non-combustible frame with a clear cover. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 2.14 | Yes | No | Handrail on rear wall of car enclouser is missing. Replace or repair. |