Inspection
Inspection Details
Equipment ID
9988
9988
Inspection Date
2/1/2022
2/1/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
b02b3f6b-947a-417e-abc8-2d1594daec30
b02b3f6b-947a-417e-abc8-2d1594daec30
Location
Railton Residence
205 N 18th St, St. Louis, MO
Phone: (314) 621-2424
205 N 18th St, St. Louis, MO
Phone: (314) 621-2424
Owner
Attn: Salvation Army- Divisional Headquarters
Salvation Army- Divisional Headquarters
1130 Hampton Ave, St. Louis, MO 63139
Phone: (000) 000-0000
Email: railtonresidence@mccormackbaron.com
Salvation Army- Divisional Headquarters
1130 Hampton Ave, St. Louis, MO 63139
Phone: (000) 000-0000
Email: railtonresidence@mccormackbaron.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | Yes | Loose buffer in pit. Rusted channel. When buffer is compressed, it stays compressed. Does not return to original position. | 5/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Car Top Alarm bell does not work | 2/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone has no dial tone | 2/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Permanent provisions shall be made to prevent accumulation of water in pit | 4/14/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Repair lighting in stairwell to roof to provide safe access to machine room | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm in car is not working. Re-inspection required | 7/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car is not working. Re-inspection required | 7/8/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection Incomplete. Need to test car buffers, counter-weight buffers, and safeties with capacity. Need to test the main brake and emergency brake with 125% capacity. (Reinspect) | 1/12/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | The fire hat light is flashing in the elevator cab when the car is in "Normal" operation. The fire hat light shall only illuminate during "Fire Fighter's" operation. The fire hat in the car shall only flash when a fire alarm initiating device in the machine room or hoistway is activated. Otherwise, the illumination shall be solid. | 1/12/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | Yes | During the 125% unintended movement test, the emergency brake failed to stop the downward movement of the car in lees than 48". The rope gripper is leaking fluid and will not reset. | 1/12/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | The fire hat light is flashing in the elevator cab when the car is in "Normal" operation. The fire hat light shall only illuminate during "Fire Fighter's" operation. The fire hat in the car shall only flash when a fire alarm initiating device in the machine room or hoistway is activated. Otherwise, the illumination shall be solid. | 6/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 5-year Inspection Incomplete. Need to test car buffers, counter-weight buffers, and safeties with capacity. Need to test the main brake and emergency brake with 125% capacity. | 6/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 5-year Inspection Incomplete. Need to test car buffers, counter-weight buffers, and safeties with capacity. Need to test the main brake and emergency brake with 125% capacity. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | The fire hat light is flashing in the elevator cab when the car is in "Normal" operation. The fire hat light shall only illuminate during "Fire Fighter's" operation. The fire hat in the car shall only flash when a fire alarm initiating device in the machine room or hoistway is activated. Otherwise, the illumination shall be solid. |