Inspection
Inspection Details
Equipment ID
2049
2049
Inspection Date
1/19/2022
1/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Christopher Hughes
Christopher Hughes
Relief Valve Pressure
374
374
Slide
Governor Rope Pull
Door Closing Force
24F 22R
24F 22R
External ID
1fa1bc35-a10b-4f7e-a0e2-22ef55803702
1fa1bc35-a10b-4f7e-a0e2-22ef55803702
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Lee's Summit R-7 School District
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency lights weak. | 1/19/2021 |
| A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3 | Yes | No | no metal data tags | 1/19/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machroom door lock defeatable | 1/19/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(k) | No | No | FFS modules in machine room missing covers. | 3/26/2026 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.11.2.1.2(hh) | No | No | Provide code data plate in machine room. | 3/26/2026 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.2.1.1(r) | Yes | No | Provide door restrictors for each car door. | 1/19/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(k) | No | No | Smoke and heat detector wiring exposed, not in conduit. | 3/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide covers for FFS modules in machine room. | 9/26/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | New smoke detectors present in machine room, but not connected to controller. | 9/26/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency battery lowering not working. Battery | 4/1/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Top of hoistway smoke recalls to wrong floor | 4/1/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Shunt trip not overriding battery lowering. Need relay added | 4/1/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency battery lowering inoperable. Bad battery | 2/20/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Shunt trip battery override needs testing with good battery | 2/20/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Shunt trip not overriding emergency battery lowering | 10/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. |